Critical flaw in Danfoss refrigeration controllers has no fix yet, and the older models will never get one
Danfoss has confirmed a critical flaw (CVE-2026-129713) in its AK-SM 800A refrigeration controllers, which run the fridges, freezers and cold rooms in supermarkets. An attacker with no password can knock the controller over remotely, and there is no fix yet. In a second advisory the company says the older AK-SC 355 and AK-SM 800 will never get one.
Danfoss published both advisories on 20 November, and CISA put out the first on 24 November with a severity score of 9.8 out of 10. CISA says there is no sign of exploitation yet. The flaw was reported by Carlo Meijer of Midnight Blue, the Dutch researcher who two weeks ago found six zero-days in the same controller. Neither CISA nor Danfoss says whether the new bug is one of them.
The box that decides when the freezer defrosts
A large supermarket has a central controller, sometimes more than one, that manages dozens of fridges, freezers and cold rooms. It sets the target temperature for each unit, schedules defrost cycles, runs the compressors and raises an alarm when something warms up. Danfoss's AK-SM 800A is one of these, managed through a web interface. The refrigeration contractor usually logs in remotely to change settings and fix faults without driving to the store. Whoever takes over the controller can defrost a freezer in the middle of the night or switch it off, and in the store it will look like an ordinary fault.
The password is in the manual
The second advisory covers the previous generation. According to Danfoss, the AK-SC 355 and AK-SM 800 shipped, in every version, with default passwords printed in the user manual. Anyone who never changed them gives full access to whoever reaches the interface. Danfoss will not patch them and asks customers to replace the fleet with AK-SM 800A units.
Spain's INCIBE-CERT rates the flaw critical and notes that CERT-FR has already confirmed intrusions on AK-SM and AK-SC controllers. Public information on those incidents does not say how the attackers got in.
France, then Britain, now Spain
On 11 and 12 October, defrost settings on refrigeration controllers at about 700 French retail sites were changed remotely. Stock was thrown out and there were at least 15 fires. France's cyber crisis centre attributed the attack to the IRGC's Shahid Kaveh unit, and Iran denies it (our earlier report). A few days ago the BBC revealed that Britain quietly pulled thousands of RDM controllers off the internet, fearing a similar wave.
On 24 November El Mundo reported that pro-Russian groups had attacked Bitzer refrigeration equipment in Spain that same day. The paper gave no details and we found no other confirmation. In the same piece, the Spanish police cyber unit described cold rooms being switched off at a factory in Zaragoza, causing EUR 170,000 in losses.
An unauthenticated CGI handler, and passwords from the manual
- CVE-2026-129713, Danfoss AK-SM 8xxA version 5.4.0 and earlier (DSA-2026-12-01, ICSA-26-328-03): stack-based buffer overflow (CWE-121) in an unauthenticated CGI handler. A crafted HTTP/S POST request corrupts memory and restarts the web server, and in Danfoss's words "hypothetically" allows code execution with web server privileges. CVSS v3.1 9.8, CVSS v4 9.3, AV:N/PR:N/UI:N.
- CVE-2026-127057, AK-SC 355 and AK-SM 800, all versions (DSA-2026-12-02): unauthorised access with default or known passwords. CVSS 9.9 per Danfoss.
- Fix: AK-SM 8xxA in version 5.5.x, no date. The same releases will remove the option to disable Strict Mode. No fix for the legacy models.
- Until then, per Danfoss and CISA: no public IP address, remote access only over VPN, Strict Mode on, and strong unique passwords.
- IOCs and PoC: none published.
What to check now
- Which Danfoss controllers you have on site, which model and which firmware.
- Whether any of them is reachable from the internet, including through the refrigeration contractor's cellular modem.
- On the legacy models: whether the default password was changed, and who holds the new one.
- On the AK-SM 800A: whether Strict Mode is on.
ICS Cyber News by email
Flashes and digests for the topics you pick. No ads.
Edited by Adam Zinger with AI assistance