Off-the-shelf AI found 66 new bugs in the network code inside OT devices. Nine months of work took 90 hours
Forescout pointed generally available AI models at 10 embedded TCP/IP stacks and confirmed 99 vulnerabilities, 66 of them new, for about $935 in model costs. Siemens building automation controllers are the first products named as affected.
“AI did not eliminate the need for expert vulnerability researchers, but it dramatically compressed the work.”Daniel dos Santos, Forescout
Nine months of work, in 90 hours
Forescout Research's Vedere Labs published "Finding Critical Infrastructure Bugs with Off-the-Shelf AI". The team built its own AI harness for embedded software and ran it against TCP/IP stacks, the networking code that sits inside OT, IoT, medical and network devices from many vendors at once.
Work that took about nine months by hand took about 90 hours. Across 10 stacks the pipeline confirmed 99 vulnerabilities, 66 of them previously unknown. Model spend for the automated static analysis was about $935, an average of $2.58 per finding.
66 new bugs the manual project missed
Forescout's manual Project Memoria began in 2020, took 18 months and found almost 100 CVEs across 14 embedded stacks. Going back over that ground with AI, the harness rediscovered 33 of the 82 known Project Memoria+ bugs (40%) and found the 66 new ones, either missed back then or in stacks not analyzed before. Forescout reported 54 of them to vendors and maintainers because it believed they still affected current versions.
Siemens was the first vendor to identify affected devices: building automation controllers in the APOGEE, Desigo and TALON lines run Nucleus NET and are susceptible to the new issues. Other vendors are still investigating. Forescout says one of the stacks still in disclosure reached end of general support in December 2025 and ends extended support in September 2027.
How the harness worked
Stage 0 prepares the target. Raw firmware needed LLM-assisted preprocessing, about 67 minutes in one case, 22 of them just for renaming functions. Static analysis then runs rule-based queries through Joern, on source code or on Ghidra decompiler output. The AI reasons about whether each finding is reachable, and a dynamic stage tries to confirm it, by compiling source or emulating the binary.
The 362 static findings became 312 unique candidates and then 99 confirmed issues. Precision ranged from 11% to 70% per stack: 47% on average for source code and 34% for binaries, or 22% if one binary that kept its symbols is removed. Stages 1 to 3 took about ten hours for all ten targets, under 40 minutes per source target and about 90 minutes per binary. Cost per finding ran from $0.95 to $4.16.
What it found, and what it missed
Memory corruption made up 49% of the bugs, integer issues 27%, input validation 16% and control flow or logic bugs 8%. By severity, 5% were critical, 47% high, 45% medium and 3% low. Core IP, TCP, UDP, ICMP and Ethernet code held 29% of the new flaws, HTTP and web servers 15%, and IPv6, Neighbor Discovery, RPL and DHCP clients 10% each. Telnet was 7%.
Forescout says the harness is good at memory safety bugs in protocol parsing and weak on design flaws such as predictable TCP initial sequence numbers, bad random number generation, DNS cache poisoning and TCP state machine issues. Published examples include FSCT-2026-0006 in lwIP, where a FIN flag copied in tcp_receive() lets a remote attacker crash the stack by connecting to an open TCP port.
What Forescout recommends
Prioritize by reachability, exploitability and operational impact. Turn off or restrict FTP, Telnet, IPv6 and web admin interfaces where possible, and point devices at internal DNS. Replace flat VPNs and shared accounts with brokered, least-privilege remote access. Put unpatchable and end-of-life devices in tightly restricted segments, with a plan to replace them. In procurement, ask suppliers for support lifetimes, a disclosure policy, SBOMs and evidence of ongoing security testing.
If finding a bug in your controller's network stack now costs a few dollars, which devices on your plant network can you never patch?