Significant vulnerability in WinCC and PCS 7: for some products no fix is planned
On 10 November 2026, Siemens ProductCERT published advisory SSA-970803 (CVE-2026-58114).
It covers SIMATIC systems that sit at the heart of many plants: WinCC, WinCC Runtime Professional, PCS 7, BATCH, Process Historian and Information Server.
This is a vendor publication about a product vulnerability. The advisory does not report exploitation, and it does not describe an attack on a specific site.
The problem, in Siemens' wording, is that remote user authentication on these systems is not properly protected when it still relies on NTLM, an older Windows protocol.
An unauthenticated attacker who has obtained a machine-in-the-middle position on the traffic path can relay that authentication and impersonate a legitimate user. That is what is called an NTLM relay.
The attacker does not need to know the password: they sit on the path, capture the authentication exchange and forward it to another service, and the service treats them as the user.
A position on the traffic path is a prerequisite according to the wording of the advisory. Siemens also points to its operational guidelines for Industrial Security, as a general recommendation for protecting network access.
Siemens writes that the extent of the harm depends on the services that can be reached, and gives as an example a SQL Server used by WinCC. The advisory summary also says the attacker could take over the session and run code with the privileges of that user.
The CVSS score is 7.5 in version 3.1 and 7.7 in version 4.0. The version 3.1 vector includes high complexity and user interaction.
The remediation column needs to be read exactly as Siemens wrote it.
For WinCC V7.5, V8.0 and V8.1, and for WinCC Runtime Professional V17 to V21 (all versions), Siemens writes that no fix is currently available, and that it is preparing fixes for products where a fix is not yet available.
For PCS 7 V9.1, BATCH V9.1, Process Historian 2020 and 2022, and Information Server 2020 and 2022 (all versions), it writes that no fix is currently planned.
The specific mitigation Siemens names is to manually configure encryption for communication with the SQL Server database, according to its support page.
In additional notes it also points to Microsoft's move away from NTLM, and states that leaving NTLM means using Kerberos, in a domain where the service principal names (SPN) are set correctly. If Kerberos is not used, Siemens writes, the corresponding risk must be assessed.
Any such change on a live control system should first be tested for operational compatibility, in a trial environment, before it is applied on the plant.
I am a consultant for control-system and critical-infrastructure cybersecurity, and I have worked inside these systems for more than twenty years.
PCS 7 V9.1 systems will remain in plants for years. When no fix is on the way, protection moves to the network around the system and to the Windows configuration.
When I design a control network I assume some components will not receive a fix, so the architecture has to protect them as well.
The full advisory: SSA-970803 on the Siemens ProductCERT site. The researcher who reported the vulnerability is Tim Dijkman of Powerspex.
If you run PCS 7 or WinCC, do you know today whether your servers still accept NTLM?